LOW VOLTAGE CABLE ( 4 CORES )

CXV/SWA 0.6/1kV

CXV/DATA 0.6/1kV

CXV/DATA 0.6/1kV

AXV 0.6/1kV

AXV 0.6/1kV

  • Power cable
  • 4 cores
  • Reduced neutral
  • Compacted copper conductor
  • Armoured (steel wire)
  • Sheathed
  • 0.6/1kV
  • Power cable
  • 4 cores
  • Reduced neutral
  • Compacted copper conductor
  • Armored (2 aluminum tapes)
  • Sheathed
  • 0.6/1kV
  • Power cable
  • 1, 2, 3, 4 cores
  • Compacted copper core
  • Armored (2 aluminum strips)
  • Sheathed
  • 0.6/1kV
  • Power cable
  • 4 cores
  • Reduced neutral
  • Compacted aluminium core
  • XLPE insulation
  • Unarmoured
  • Sheathed
  • 0.6/1kV
  • Power cable
  • 1, 2, 3, 4 cores
  • Compacted aluminum core
  • XLPE insulation
  • Unarmored
  • Sheathed

Cable Characteristics:

Cable Characteristics:

Cable Characteristics:

Cable Characteristics:

Cable Characteristics:

  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature in normal operation: 90 o C
  • Maximum conductor temperature during short circuit for maximum 5s: 250 o C
  • Minimum bend radius: 12 x D (D: outer diameter of cable)
  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature in normal operation: 90 o C
  • Maximum conductor temperature during short circuit for maximum 5s: 250 o C
  • Minimum bend radius: 12 x D (D: outer diameter of cable)
  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature in normal operation: 90 o C
  • Maximum conductor temperature during short circuit for maximum 5s: 250 o C
  • Minimum bend radius: 12 x D (D: outer diameter of cable)
  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature in normal operation: 90 o C
  • Maximum conductor temperature during short circuit for maximum 5s: 250 o C
  • Minimum bend radius: 8 x D (D: outer diameter of cable)
  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature in normal operation: 90 o C
  • Maximum conductor temperature during short circuit for maximum 5s: 250 o C
  • Minimum bend radius: 8 x D (D: outer diameter of cable)

AVV 0.6/1kV

CXV 0.6/1kV

CXV 0.6/1kV

CXV 0.6/1kV

CXV 0.6/1kV

  • Power cable
  • 4 cores
  • Reduced neutral
  • Compacted aluminum core
  • PVC insulation
  • Unarmored
  • Sheathed
  • 0.6/1kV
  • Power cable
  • 4 cores
  • Reduced neutral
  • Compacted copper conductor
  • XLPE insulation
  • Unarmored
  • Sheathed
  • Power cable
  • 4 cores
  • Reduced neutral
  • Copper conductor
  • XLPE insulation
  • Unarmored
  • Sheathed
  • Power cable
  • 1, 2, 3, 4 cores
  • Compacted copper core
  • XLPE insulation
  • Unarmored
  • Sheathed
  • Power cable
  • 1, 2, 3, 4 cores
  • Copper core
  • XLPE insulation
  • Unarmored
  • Sheathed
  • 0.6/1kV

Cable Characteristics:

Cable Characteristics:

Cable Characteristics:

Cable Characteristics:

Cable Characteristics:

  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature in normal operation: 70 o C
  • Maximum conductor temperature during short circuit for maximum 5s:
    • For conductor cross section > 300 mm2: 140 0 C
    • For conductor cross section ≤ 300 mm2: 160 0 C
  • Minimum bend radius: 8 x D (D: outer diameter of cable)
  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature in normal operation: 90 o C
  • Maximum conductor temperature during short circuit for maximum 5s: 250 o C
  • Minimum bend radius: 8 x D (D: outer diameter of cable)
  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature in normal operation: 90 o C
  • Maximum conductor temperature during short circuit for maximum 5s: 250 o C
  • Minimum bend radius: 8 x D (D: outer diameter of cable)
  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature in normal operation: 90 o C
  • Maximum conductor temperature during short circuit for maximum 5s: 250 o C
  • Minimum bend radius: 8 x D (D: outer diameter of cable)
  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature in normal operation: 90 o C
  • Maximum conductor temperature during short circuit for maximum 5s: 250 o C
  • Minimum bend radius: 8 x D (D: outer diameter of cable)

CVV 0.6/1kV

CVV 0.6/1kV

DK-CVV 0.6/1kV

  • Power cable
  • 4 cores
  • Reduced neutral
  • Compacted copper conductor
  • PVC insulation
  • Unarmored
  • Sheathed
  • Power cable
  • 4 cores
  • Reduced neutral
  • Copper conductor
  • PVC insulation
  • Unarmored
  • Sheathed
  • 0.6/1kV
  • Meter cable
  • 4 cores
  • Reduced neutral
  • Copper conductor
  • PVC insulation
  • Aluminum tape armor
  • PVC sheath

Cable Characteristics:

Cable Characteristics:

Cable Characteristics:

  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature in normal operation: 70oC
  • Maximum conductor temperature during short circuit for maximum 5s:
    • For conductor cross section > 300 mm2: 1400C
    • For conductor cross section ≤ 300 mm2: 1600C
  • Minimum bend radius: 8 x D (D: outer diameter of cable)
  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature in normal operation: 70 o C
  • Maximum conductor temperature during short circuit for maximum 5s:
    • For conductor cross section > 300 mm2: 140 0 C
    • For conductor cross section ≤ 300 mm2: 160 0 C
  • Minimum bend radius: 8 x D (D: outer diameter of cable)
    • Rated voltage (Uo/U): 0.6/1kV
    • Maximum conductor temperature in normal operation: 70 o C
    • Maximum conductor temperature during short circuit for maximum 5s:
      • For conductor cross section > 300 mm2: 140 0 C
      • For conductor cross section ≤ 300 mm2: 160 0 C
    • Minimum bend radius: 10 x D (D: outer diameter of cable)