FIRE RESISTANT CABLES

FMR – Cu/XLPE/CTS/FR-PVC 0.6/1kV

FMH -Cu/XLPE/FR-PVC/DSTA/FR-PVC 0.6/1kV

FMC – Cu/FR-PVC/FR-PVC 0.6/1kV

FMC – Cu/FR-PVC/FR-PVC 0.6/1kV

FMB – Cu/XLPE/FR-PVC 0.6/1kV

  • Control cable
  • Flame retardant
  • XLPE insulated
  • Screened
  • Flame retardant cable
  • 4 cores
  • Reduced neutral
  • XLPE insulated
  • Armored (2 steel tapes)
  • Sheathed
  • Flame retardant cable
  • 4 cores
  • Reduced neutral
  • FR-PVC insulated
  • Unarmored
  • Sheathed
  • Flame retardant cable
  • 1, 2, 3, 4 cores
  • FR-PVC insulated
  • Unarmored
  • Sheathed
  • Flame retardant cable
  • 4 cores
  • Reduced neutral
  • XLPE insulated
  • Unarmored
  • Sheathed

Cable Characteristics:

Cable Characteristics:

Cable Characteristics:

Cable Characteristics:

Cable Characteristics:

  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature: 90 0 C in normal operation, 250 0 C short circuit maximum for 5s
  • Minimum bend radius: 8xD (8 times the outer diameter of the cable)
  • Flame retardant: IEC 60332-1
  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature: 90 0 C in normal operation, 250 0 C short circuit maximum for 5s
  • Minimum bend radius: 12xD (12 times the outer diameter of the cable)
  • Flame retardant: IEC 60332-1; IEC 60332-3-24
  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature: 70 0 C in normal operation
  • Minimum bend radius: 8xD (8 times the outer diameter of the cable)
  • Flame retardant: IEC 60332-1; IEC 60332-3-24
  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature: 70 0 C in normal operation
  • Minimum bend radius: 8xD (8 times the outer diameter of the cable)
  • Flame retardant: IEC 60332-1; IEC 60332-3-24
  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature: 90 0 C in normal operation, 250 0 C short circuit maximum for 5s
  • Minimum bend radius: 8xD (8 times the outer diameter of the cable)
  • Flame retardant: IEC 60332-1; IEC 60332-3-24

FMA – Cu/FR-PVC 0.6/1kV

FLH – Cu/XLPE/LSZH/DSTA/LSZH 0.6/1kV

FLB – Cu/XLPE/LSZH 0.6/1kV

FRH – Cu/Mica/XLPE/FR-PVC/DSTA/FR-PVC 0.6/1kV

FRB – Cu/Mica/XLPE/FR-PVC 0.6/1kV

  • Flame retardant cable
  • 1 core
  • FR-PVC insulated
  • Unarmored
  • Unsheathed
  • Flame retardant
  • Low smoke halogen free
  • 2, 3, 4 core
  • XLPE insulated
  • Armored (2 steel tapes)
  • Sheathed cable
  • Flame retardant
  • low smoke halogen free
  • 4 cores
  • Reduced neutral
  • XLPE insulated
  • Unarmored
  • Sheathed cable
  • Fire resistant cable
  • 2, 3, 4 cores
  • XLPE insulated
  • Armored (2 steel tapes)
  • Sheathed
  • Fire resistant cable
  • 4 cores
  • Reduced neutral
  • XLPE insulated
  • Unarmored
  • Sheathed

Cable Characteristics:

Cable Characteristics:

Cable Characteristics:

Cable Characteristics:

Cable Characteristics:

  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature: 70 0 C in normal operation
  • Minimum bend radius: 8xD (8 times the outer diameter of the cable)
  • Flame retardant: IEC 60332-1; IEC 60332-3-24
  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature: 90 0 C in normal operation, 250 0 C short circuit maximum for 5s
  • Minimum bend radius: 12xD (12 times the outer diameter of the cable)
  • Flame retardant: IEC 60332-1; IEC 60332-3-24
  • Acid gas generation (HCl): IEC 60502-1; IEC 60754-1
  • Fluorine content: IEC 60502-1; IEC 60684-2
  • Conductivity and pH: IEC 60502-1; IEC 60754-2
  • Smoke emission: IEC 61034-2
  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature: 90 0 C in normal operation, 250 0 C short circuit maximum for 5s
  • Minimum bend radius: 8xD (8 times the outer diameter of the cable)
  • Flame retardant: IEC 60332-1; IEC 60332-3-24
  • Acid gas generation (HCl): IEC 60502-1; IEC 60754-1
  • Fluorine content: IEC 60502-1; IEC 60684-2
  • Conductivity and pH: IEC 60502-1; IEC 60754-2
  • Smoke emission: IEC 61034-2
  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature: 90 0 C in normal operation, 250 0 C short circuit maximum for 5s
  • Minimum bend radius: 12xD (12 times the outer diameter of the cable)
  • Fire resistance: IEC 60331
  • Flame retardant: IEC 60332-1
  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature: 90 0 C in normal operation, 250 0 C short circuit maximum for 5s
  • Minimum bend radius: 8xD (8 times the outer diameter of the cable)
  • Fire resistance: IEC 60331
  • Flame retardant: IEC 60332-1

FRA – Cu/Mica/FR-PVC 0.6/1kV

FID-Cu/Mica/XLPE/LSZH/SWA/LSZH 0.6/1kV

FID – Cu/Mica/XLPE/LSZH/SWA/LSZH 0.6/1kV

FIC – Cu/Mica/XLPE/LSZH 450/750V

  • Fire resistant cable
  • 1 core
  • FR-PVC insulated
  • Unarmored
  • Unsheathed
  • Fire resistant
  • Low smoke zero halogen cable
  • 5 cores
  • XLPE insulated
  • Armoured (steel wire)
  • Sheathed
  • Fire resistant
  • Low smoke zero halogen cable
  • 2, 3, 4 cores
  • XLPE insulated
  • Armored (steel wire)
  • Sheathed
  • Fire resistant
  • Low smoke zero halogen cable
  • 2, 3, 4, 5 cores
  • XLPE insulated
  • Unarmored
  • Sheathed

Cable Characteristics:

Cable Characteristics:

Cable Characteristics:

Cable Characteristics:

  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature: 70 0 C in normal operation
  • Minimum bend radius: 8xD (8 times the outer diameter of the cable)
  • Fire resistance: IEC 60331
  • Flame retardant: IEC 60332-1
  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature: 90 0 C in normal operation, 250 0 C short circuit maximum for 5s
  • Minimum bend radius: 12xD (12 times the outer diameter of the cable)
  • Fire resistance: IEC 60331; BS 6387
  • Flame retardant: BS EN 60332-1; IEC 60332-1
  • Acid and corrosive gas generation: BS 7846; BS 50267-2-1; IEC 60754-1&2
  • Smoke emission: BS 7846; BS EN 50268-2; IEC 61034-2 
  • Rated voltage (Uo/U): 0.6/1kV
  • Maximum conductor temperature: 90 0 C in normal operation, 250 0 C short circuit maximum for 5s
  • Minimum bend radius: 12xD (12 times the outer diameter of the cable)
  • Fire resistance: IEC 60331; BS 6387
  • Flame retardant: BS EN 60332-1; IEC 60332-1
  • Acid and corrosive gas generation: BS 7846; BS 50267-2-1; IEC 60754-1&2
  • Smoke emission: BS 7846; BS EN 50268-2; IEC 61034-2
  • Rated voltage (Uo/U): 450/750V
  • Maximum conductor temperature: 90 0 C in normal operation, 250 0 C short circuit maximum for 5s
  • Minimum bend radius: 8xD (8 times the outer diameter of the cable)
  • Fire resistance: IEC 60331; BS 6387
  • Flame retardant: IEC 60332-1
  • Acid and corrosive gas generation: BS 7211; BS 50267-2-1; IEC 60754-1&2
  • Smoke emission: BS 7211; BS EN 50268-2; IEC 61034-2